230426-PO-City-Hall-Addendum-03City of Port Orchard City Hall Building Improvements ADDENDUM #3 April 26, 2023 TO ALL BIDDERS: The Bid Documents issued April 7, 2023 for the project noted above are amended by this Addendum #3. Receipt of this addendum shall be acknowledged by inserting its number in the space provided on the bid form. PROJECT MANUAL ITEMS ITEM 1. Specification Section 263200 — Generator a. Acceptable Manufacturers Section 1.4 — Add Energy System Power Systems (Generac) ITEM 2. Specification Section 263623 — Automatic Transfer Switch a. Acceptable Manufacturers Section 1.4.13 — Add Energy System Power Systems (Generac) DRAWINGS ELECTRICAL ITEM 1. Sheet E00.01 — Replace Sheet a. Added approved substitutions for light fixtures GENERAL QUESTIONS ITEM 2. While talking to the rep for American Fiber Cement I found out that they don't have the lap siding but they will rip their panel siding to make the lap siding. 10' is the longest length they can provide, and each joint requires a 3/8" space that cannot be caulked. There's a lot of footage of this lap siding which means a lot of 3/8" gaps. Will the gaps be left open, or can a detail be provided to cover them? a. The gaps will be left open per the manufacturer's recommendations. Butt joint gaps are to be staggered to reduce joint visibility. ITEM 3. The attachment is page 3 of the Fiber Cement Spec. It lists Sealant and metal trims to match the siding. The manufacturer does not allow any sealant at the joints, and they do not provide any metal trims that are listed in this spec. a. The gaps will not be closed or concealed with metal. Installation details will be per the manufacturer's recommendations. Port Orchard City Hall - Building Improvements Addendum #1 Page 2 ITEM 4. 1 need Strongirt to provide an engineered system for the attachment of the girts to the existing metal studs. However, I need a stud gauge in order for them to do this. Can you please provide the metal stud gauge for the existing exterior metal studs? a. Use 20 gauge as the existing stud gauge. ITEM 5. Should we schedule a waterproofing representative to conduct a Rilem Tube Test? If so, who do I contact from the city to schedule a site visit to conduct the test? a. If you wish to test the brick prior to bid, please contact Chris Hammer to schedule the test. His phone number is 360-876-4991 or kchammer(cDportorchardwa.gov. You will be required to visit the Public Works desk to sign in prior to the test. This is the same location as the pre -bid walk-through. ITEM 6. BCC-2 is located inside the Bid Alternate # 2 zone, but (14) of the IHP's it serves are located outside of the Bid Alternate # 2 zone. How should we breakout the pricing for this system since it is both included in the base bid area and alternate # 2 bid area? a. BCC-2S is not located within the Bid Alternate #2 area on Level 2. However, the base bid includes all Mechanical shown on the drawings. Bid Alternates, if selected, will simply relocate a register or 2 to accommodate the new wall locations if applicable. No additional mechanical equipment is part of the bid alternates. ITEM 7. BCC-3S is located inside the Bid Alternate # 3 zone, but (10) of the IHP's it serves are located outside of the Bid Alternate # 3 zone. How should we breakout the pricing for this system since it is both included in the base bid area and alternate # 3 bid area? a. Similar to ITEM 5. All the Mechanical equipment is part of the base bid. Bid Alternate #3 is simply revising the window areas to the Court Room Office and some finishes. No additional mechanical work is to be included in this bid alternate. END OF ADDENDUM #3 LIGHTING FIXTURE SCHEDULE �1 ELECTRICAL SYMBOLS LEGEND C TYPE MANUFACTURER LAMPS WATTS MOUNTING > A DETAIL/SECTION IDENTIFICATION: A = DETAIL/SECTION LETTER, B = SHEET NUMBER SM WIRELESS LIGHT SWITCH, SINGLE POLE, SUBSCRIPTS; 3 = THREE WAY, 4 = B WHERE DETAIL/SECTION IS DRAWN. FOUR WAY, D = DIMMER CONTROL, a, b, c, ETC = NUMBER OF SWITCHES AT Al METALUX LED 46 RECESSED THE LOCATION AND SPECIFIC FIXTURES CONTROLLED. MOUNT AT 42 CC 24CZ-LD5-55-UNV-L835-CD-1 1 A EQUIPMENT CONNECTION CALLOUT. A,B EQUAL EQUIPMENT IDENTIFICATION ON INCHES AFF. C > B MECHANICAL OR KITCHEN EQUIPMENT CONNECTION SCHEDULES. VERIFY EXACT C LITHONIA > EQUIPMENT REQUIREMENTS ON SHOP DRAWING EQUIPMENT SUBMITTALS PRIOR TO ST DIGITAL 0-12 HOUR TIMER SWITCH. WATTSTOPPER TS-400 OR EQUAL 2BLT4-60L-GZ1-LP835 > ROUGH -IN. DO NO ROUGH -IN FOR EQUIPMENT PRIOR TO REVIEW OF SUBMITTALS. 1 REPORT ANY DIFFERENCES IN REQUIREMENTS TO ENGINEER IN WRITING. A1X SAME AS TYPE Al WITH Sy AUTOMATIC/MANUAL OCCUPANCY SENSOR AND SINGLE POLE TOGGLE CEMERGENCY BATTERY PACK CONDUIT CONCEALED. HASH MARKS INDICATE NUMBER OF #12 CONDUCTORS IN SWITCH. WATT STOPPER DW-100 OR EQUAL. SWITCH SHALL BE �( CODE SIZE CONDUIT. NO HASH MARKS INDICATES 2412 CONDUCTORS PLUS GROUND PROGRAMMED FOR MANUAL ON, AUTOMATIC OFF. A2 METALUX LED 36 RECESSED IN 3/4" CONDUIT, LONG HASH MARKS INDICATES NEUTRAL CONDUCTOR.0/ INDICATES \ C 22CZ-LD5-39-UNV-L835-CD-1 J GROUND CONDUCTOR. OS WIRELESS DUAL TECHNOLOGY AUTOMATIC OCCUPANCY SENSOR DEVICE. (\ LITHONIA � FLEXIBLE RACEWAY, PROVIDE GROUND CONDUCTORS PER NEC. PS WIRELESS DAYLIGHT PHOTOSENSOR r 2BLT2-40L-ADP-GZ1-LP835 A-1,3 ADJACENT TO ARROW INDICATES HOMERUN OF CONDUCTORS IN CONDUIT FOR ❑J DISCONNECT SWITCH A2X SAME AS TYPE A2 WITH CIRCUITS 1 AND 3 TO PANEL "A". ` EMERGENCY BATTERY PACK ) ® EXIT LIGHT WITH BATTERY, UNIVERSAL MOUNTING. FUSED DISCONNECT SWITCH WITH FUSES. A3 METALUX LED 37 SURFACE 4WPLD4035R EMERGENCY FLOODLIGHT WITH BATTERY. Sm MOTOR RATED TOGGLE SWITCH WITH OVERLOAD HEATER(S), SIZE PER LITHONIA � NEC AND MANUFACTURERS REQUIREMENTS. BLWP4-4800L-ADP-GZ1-LP835 � � LIGHT FIXTURE, SURFACE MOUNTED ON CEILING. C 1 xxx AVAILABLE FAULT CURRENT ( A3X SAME AS TYPE A3 WITH l LIGHT FIXTURE, RECESS MOUNTED IN CEILING. ( EMERGENCY BATTERY PACK LIGHT FIXTURE, WITH EMERGENCY BATTERY PACK. TRANSIENT VOLTAGE SURGE SUPPRESSION. TPS3-X-1 1-1 5-D2, SIEMENS OR s EQUAL. "X" =VOLTAGE/ PHASE (VARIES), SEE POWER RISER DIAGRAM C A4 METALUX LED 4SNLED-LD5-41SL-LW- 35 SURFACE J � 4 LIGHT FIXTURE, WALL MOUNTED. AND/OR PANEL SCHEDULES FOR VOLTAGE AND PHASE REQUIREMENTS. UNV-L835-CD-1 C1 DOWNLIGHT FIXTURE. (E) EXISTING LITHONIA l C CLX-L48-4000LM-SEF-FDL-MVOLT-GZ10-35K-80CR1-WH ) ❑H WALL MOUNT LIGHT FIXTURE. WP WEATHERPROOF C C A5 METALUX LED 25 WALL l JUNCTION BOX. 2BCLED-LD4-20SL-F-UNV-L835-CD-1 C 1 Al LIGHT FIXTURE TYPE. Al = SPECIFIC LIGHTING FIXTURE REFERENCED ON LIGHTING C LITHONIA / FIXTURE SCHEDULE. BLWP2-20L-ADP-GZ1-LP835 POWER PANEL A6 METALUX LED 37 WALL C C 4BCLED-LD4-36SL-F-UNV-L835-CD-1 ) DUPLEX RECEPTACLE 20A, 125 VOLT WALL MOUNTED AT 18 INCHES AFF. G = GROUND FAULT INTERRUPTING, T = TAMPERPROOF. ) LITHONIA CC BLWP4-40L-ADP-GZ1-LP835 DUPLEX RECEPTACLE 20A, 125 VOLT WALL MOUNTED HORIZONTALLY 2" ABOVE ) COUNTERTOP BACKSPLASH TO THE BOTTOM OF THE RECEPTACLE COVERPLATE. C A7 METALUX LED 50 SUSPENDED C 8TSNLED-LD5-67SL-LW- � FOURPLEX RECEPTACLE 20A, 125 VOLT, WALL MOUNTED AT 18 INCHES AFF. UNV-L835-CD-1 CC LITHONIA SPECIAL RECEPTACLE. AMPERAGE AND VOLTAGE AS SHOWN. CLX-L96-6000LM-SEF-FDL-MVOLT-GZ10-35K-80CR1-WH ® EQUIPMENT CONNECTION. PROVIDE PER NEC AND MANUFACTURERS REQUIREMENTS A8 PINNACLE LED 42 SUSPENDED AND/OR RECOMMENDATIONS. CDI-BW-835-835-7-AC_ST- C U-EL1-0-S-FE C C LUMENWERX TYPE MANUFACTURER LAMPS WATTS MOUNTING TYPE MANUFACTURER LAMPS WATTS MOUNTING CAVSPDI-OP-RLO-W102-SW-80-500-500-35-7FT-UNV-D1-1-XX-AL C A13 AXIS LIGHTING LED 60 WALL D1 AXIS LIGHTING LED 48 PENDANT C A8X SAME AS TYPE A8 WITH TB3WDLED-600-80-35-SO- ARC LIE D-SL80/20-1000-80-35-SO- J EMERGENCY BATTERY PACK 12'-AP-UNV-DP-1 4-AP-UNV-DP-1-XX ) C A9 PINNACLE LED 30 SUSPENDED A -LIGHT LUMENWERX C CDI-BW-835-835-5-AC_ST- ALD3ST-12-LS-35-U-HE-R-T-D SMIPICL-PMO-LED-80-200LMF-1800LMG-40-4FT-UNV-D1-1-XXX-AL / 1 C U-EL1-0-S-FE METALUX LED 38 SURFACE D1X SAME AS TYPE D1 WITH CA14 LUMENWERX 22FP4235C-FPXSURF22 EMERGENCY BATTERY PACK ` ( CAVSPDI-OP-RLO-W102-SW-80-500-500-35-5FT-UNV-D1-1-XX-AL ) C LITHONIA E1 VISTA PROFESSIONAL LIGHTING LED 35 IN -GRADE A10 AXIS LIGHTING LED 20 WALL CPX-2X2-4000LM-80CR1-35K-SW L-MIN 10-ZT-MVOLT/l X4SM KS H 1188-Z-M F-40-B-MV-AX- C TB3WDLED-600-80-35-SO- ND-B34-T015-DF C 4'-AP-UNV-DP-1 A14X SAME AS TYPE A14 WITH EMERGENCY BATTERY PACK HYDREL C A -LIGHT M9410C-A-LED-P4-40K-MVOLT-MFL-FLC20SR-34B-BZ ALD3ST-4-LS-35-U-HE-R-T-D A15 FAIL-SAFE LED 74 RECESSED CFMDR-D-12-4-LD4-2-STD-35-UNV- E2 VISTA PROFESSIONAL LIGHTING LED 35 IN -GRADE A10X SAME AS TYPE Al WITH 81 -XX-E D D- 1 -SWB R-VRS D 1188-Z-NS-40-B-MV-AX- C EMERGENCY BATTERY PACK ND-B34-T010-DF NEW STAR LIGHTING C All AXIS LIGHTING LED 10 WALL 37M-lX4-B-B-L3-35-lC-OA-UN-DM-AH HYDREL TB3WDLED-600-80-35-SO- M9410C-A-LED-P4-40K-MVOLT-NSP-FLC10SR-34B-BZ C2'-AP-UNV-DP-1 A15X SAME AS TYPE A15 WITH l ` ( EMERGENCY BATTERY PACK E3 TRULY GREEN SOLUTIONS LED 80 FLOODLIGHT ) A -LIGHT IPF-S-40-U-D-05-KN-IPF-S-TV C ALD3ST-2-LS-35-U-HE-R-T-D B1 HALO LED 8 RECESSED l I ( LT4-06-9FS23-1 E-WH-DM LITHONIA Al2 AXIS LIGHTING LED 40 WALL DSXF1-P2-40K-FL-MVOLT-THK-UBV-DDBXD C TB3WDLED 600 80 35 SO B2 HALO LED 10 RECESSED l ` 8'-AP-UNV-DP-1 HC6R-10-D010-HM6R-0525- E4 ILP LIGHTING LED 35 SURFACE ) 835-62R-MD-C (RETROFIT) WTZ4-5L-40-MWUSBD A -LIGHT ALD3ST-8-LS-35-U-HE-R-T-D LITHONIA NEW STAR LIGHTING �) C LDN6RV-35/10-LR-6-AR-LS-MVLT-GZ1-TRW VTW4-ST-40-FP-UN-OC Al2X SAME AS TYPE Al2 WITH l EMERGENCY BATTERY PACK Cl 2'x4', DECORATIVE, LED, PENDANT LED 50 PENDANT X1 SURE-LITES INCLUDED 35 UNIVERSAL J MOUNT, TO MATCH EXISTING CX71 C2 Vx4', DECORATIVE, LED, PENDANT LED 35 PENDANT MOUNT, TO MATCH EXISTING RICfe"guSII &HR architecture interiors planning vizlab 275 FIFTH STREET, SUITE 100 BREMERTON, WA 98337 360-377-8773 RFMARCH.COM CROSS ENGINEERS, INC 923 MLK Jr. Way Tacoma, WA 98405 e=====iq g info@crossengineers.com Phone: (253) 759-0118 Job Number: 20-125 N L. C-)���� 0029060 i a/sT 4/25/23 J J Cn w C0 00 az = W U LU� F--� W 0 ~ wQ C> > 0 = ") O Uc) 0-0 Q 0 N 0 0 w 0 0 F_ w 0 PROJECT # 2020013 BID DOCUMENTS ISSUE DATE MARCH 31, 2023 ELECTRICAL SYMBOLS LEGEND/ LIGHT FIXTURE SCHEDULE SHEET # E00n01